SMA-Sunny Boy 4000TL

New

More info

  Sunny Boy
3000TL
Sunny Boy
4000TL
Sunny Boy
5000TL
Input (DC)      
Max. DC power (@ cos φ=1) 3200 W 4200 W* 5250 W**
Max. input voltage 750 V 750 V 750 V
MPP voltage range / rated input voltage 175 V – 500 V / 400 V 175 V – 500 V / 400 V 175 V – 500 V / 400 V
Min. input voltage / initial input voltage 125 V / 150 V 125 V / 150 V 125 V / 150 V
Max. input current input A / input B 15 A / 15 A 15 A / 15 A 15 A / 15 A
Max. input current per string input A / input B 15 A / 15 A 15 A / 15 A 15 A / 15 A
Number of independent MPP inputs / strings per MPP input 2 / A:2; B:2 2 / A:2; B:2 2 / A:2; B:2
       
Output (AC)      
Rated output power (@ 230 V, 50 Hz) 3000 W 4000 W 4600 W
Max. apparent AC power 3000 VA 4000 VA 5000 VA***
Nominal AC voltage / range 220 V, 230 V, 240 V / 180 V – 280 V 220 V, 230 V, 240 V / 180 V – 280 V 220 V, 230 V, 240 V / 180 V – 280 V
AC power frequency / range 50 Hz, 60 Hz / -5 Hz ... +5 Hz 50 Hz, 60 Hz / -5 Hz ... +5 Hz 50 Hz, 60 Hz / -5 Hz ... +5 Hz
Rated power frequency / rated power voltage 50 Hz / 230 V 50 Hz / 230 V 50 Hz / 230 V
Max. output current 16 A 22 A 22 A
Power factor at rated power 1 1 1
Adjustable displacement factor 0.8 overexited ... 0.8 underexited 0.8 overexited ... 0.8 underexited 0.8 overexited ... 0.8 underexited
Feed-in phases / connection phases 1 / 1 1 / 1 1 / 1
       
Efficiency      
Max. efficiency / European efficiency 97 % / 96.0 % 97 % / 96.4 % 97 % / 96.5 %
       
Protection      
Input-side disconnection device yes yes yes
Ground-fault monitoring / grid monitoring yes / yes yes / yes yes / yes
DC surge arrester Type II, can be integrated
DC reverse-polarity protection / AC short-circuit current capability / galvanically isolated yes / yes / — yes / yes / — yes / yes / —
All-pole sensitive residual current monitoring unit yes yes yes
Protection class (according to IEC 62103) / overvoltage category (according to IEC 60664-1) I / III I / III I / III
       
General Data      
Dimensions (W / H / D) 490 / 519 / 185 mm
(19.3 / 20.4 / 7.3 inch)
490 / 519 / 185 mm
(19.3 / 20.4 / 7.3 inch)
490 / 519 / 185 mm
(19.3 / 20.4 / 7.3 inch)
Weight 26 kg / 57.3 lb 26 kg / 57.3 lb 26 kg / 57.3 lb
Operating temperature range -25 °C ... +60 °C / -13 °F ... +140 °F -25 °C ... +60 °C / -13 °F ... +140 °F -25 °C ... +60 °C / -13 °F ... +140 °F
Noise emission (typical) 25 dB(A) 25 dB(A) 25 dB(A)
Self-consumption (night) 1 W 1 W 1 W
Topology Transformerless Transformerless Transformerless
Cooling concept Convection Convection Convection
Degree of protection (according to IEC 60529) IP65 IP65 IP65
Degree of protection of connection area (according to IEC 60529) IP54 IP54 IP54
Climatic category (according to IEC 60721-3-4) 4K4H 4K4H 4K4H
Maximum permissible value for relative humidity (non-condensing) 100 % 100 % 100 %
       
Features      
DC terminal SUNCLIX SUNCLIX SUNCLIX
AC terminal Spring-type terminal Spring-type terminal Spring-type terminal
Display Graphic Graphic Graphic
Interface: RS485 / Bluetooth opt. / yes opt. / yes opt. / yes
Warranty: 5 / 10 / 15 / 20 / 25 years yes / opt. / opt. / opt. / opt. yes / opt. / opt. / opt. / opt. yes / opt. / opt. / opt. / opt.
Multi-function relay opt. opt. opt.
Certificates and approvals (more available on request) CE, VDE0126-1-1, C10/11, VDE-AR-N 4105 CE, VDE0126-1-1, C10/11, VDE-AR-N 4105 CE, VDE0126-1-1, C10/11, VDE-AR-N 4105
       
* 4000 W with VDE-AR-N 4105
** 4600 W with VDE-AR-N-4105
*** 4600 VA with VDE-AR-N 4105
     
Provisional data, as of December 2011
Data at nominal conditions
     
Type designation SB 3000TL-21 SB 4000TL-21 SB 5000TL-21
 
 